Market Leading block loading capability.
Conform to ISO:8528-5 steady state and transient response requirement.
Reliable, Rugged, Durable design - long service intervals between scheduled maintenance.
Lower cost of Ownership - cap in end user cost.
Optimised Fuel consumption over a range of load.
Prime Power Output |
Engine Manufacturer |
Engine Model |
Gross Engine Power |
Engine Cooling System |
No.of Cylinder and Position |
Displacement | Aspiration |
---|---|---|---|---|---|---|---|
1250 kVA / 1000 kW |
Perkins | 4012-46TAG0A | 1117 kWm | Liquid Cooled | 12, 60◦ Vee | 45.8 Litre | Turbocharged air to air charge cooled |
Bore x Stroke | Recommended Fuel |
Combustion System |
Compression Ratio |
Total Lubricating Capacity |
Total Coolant Capacity |
Specific Fuel Consumption (g/ kWh) |
|
160 x 190 mm | HSD | Direct Injection | 13:01 | 177 Litre | 207 Litre | 100%Load : 197 75 % Load : 201 50% Load : 208 |
|
Alternator Rated Power |
Rated Voltage (L-L) |
Frequency | Rated Speed |
Rated Current |
Power Factor |
Poles | Phase |
1250 kVA | 415 V | 50 Hz | 1500 rpm | 1739 amp | 0.8 (lagging) | 4 | 3 |
Insulation Class | Temperature Rise Limit |
Protection | Voltage Regulation |
Over Load Capability |
Excitation System |
||
Class H | Class H | IP 23 | ± 1% | 10% for 1 hour in every 12 hours operation |
Brushless |
Prime Power Output | 1250 kVA / 1000 kW |
---|---|
Engine Manufacturer | Perkins |
Engine Model | 4012-46TAG0A |
Gross Engine Power | 1117 kWm |
Engine Cooling System | Liquid Cooled |
No.of Cylinder and Position | 12, 60◦ Vee |
Displacement | 45.8 Litre |
Aspiration | Turbocharged air to air charge cooled |
Bore x Stroke | 160 x 190 mm |
Recommended Fuel | HSD |
Combustion System | Direct Injection |
Compression Ratio | 13:01 |
Total Lubricating Capacity | 177 Litre |
Total Coolant Capacity | 207 Litre |
Specific Fuel Consumption (g/kWh) | 100%Load : 197 75 % Load : 201 50% Load : 208 |
Alternator Rated Power | 1250 kVA |
Rated Voltage (L-L) | 415 V |
Frequency | 50 Hz |
Rated Speed | 1500 rpm |
Rated Current | 1739 amp |
Power Factor | 0.8 (lagging) |
Poles | 4 |
Phase | 3 |
Insulation Class | Class H |
Temperature Rise Limit | Class H |
Protection | IP 23 |
Voltage Regulation | ± 1% |
Over Load Capability | 10% for 1 hour in every 12 hours operation |
Excitation System | Brushless |